Title |
Study on the Measurement of Radiation Energy of the Arc in GCBs |
Authors |
송기동(Song, Ki-Dong) ; 오연호(Oh, Yeon-Ho) ; 정진교(Chong, Jin-Kyo) ; 조용성(Cho, Young-Sung) |
Keywords |
PM-Tube ; Radiation ; Arc ; SF_6 gas ; GCB |
Abstract |
A special PM-Tube(Photo Multiplier Tube) that is using the photoelectric effect has been designed and manufactured to measure the radiation energy of arc in a gas circuit breaker(GCB). The PM-Tube, LLG(liquid light guides), ND(neutral density) filter, and a model gas circuit breaker have been combined for the reception and the transmission of the light and a simplified synthetic test facility with the arc energy measuring system has been established. In the case of SF_6 gas pressure 5kg.f/cm^2 and arc length 20mm, the radiation energy increases with the arc current but it tend to be saturated in the above 20kA. Under the arc current 20kA, the total radiation energy has the biggest value around 8kA and was not exceeded 40% of the total arc energy. |