Title The Characteristics of UV Generation and Aging Materials in According to Surface Discharge
Authors 송길목(Shong, Kil-Mok) ; 방선배(Bang, Sun-Bae) ; 김종민(Kim, Chong-Min) ; 김영석(Kim, Young-Seok) ; 정진수(Jung, Jin-Su)
Page pp.1606-1611
ISSN 1975-8359
Keywords Insulator ; UV ; Diagnosis ; Discharge ; EPDM
Abstract Recently, The diagnosis techniques of electric facilities are developed on live line. This paper describes the discharge characteristics of polymer insulator(EPDM A type). Keeping the facilities in good working order, the goal of this paper will provide the information to enable user to easily judge conditions of facilities on the spot. The performance of polymer insulator is assessed from the KS C IEC 60270 and CEA LWIWG-01(96)(Tracking Wheel Test). As the results, UV generation patterns of polymer insulator grow like a jellyfish shape follow the ramping voltage. Discharging UVs are detected at about 31.25% of breakdown voltage. Just then, dimension of UV image is about 0.84cm^{2}. The dimension of max. UV image is about 297.4cm^{2} at 160kV(V_{bd}). The position of UV generation due to surface discharge of polymer insulator is the center of insulator in the early, then moved the ground side and the last, UV image moved through the junction part of source side. Surface of aged polymer insulator is cracked and faded due to arc. UV absorption spectrum of polymer insulator are appeared the C-H bond of scissoring vib. at 1014cm^{-1} and C=O bond of recombination structure. Also, recombined UV absorption peak such as C-H, N-H, and O-H is detected at the 3321cm^{-1}. Through the paper, there are inspection data which are the relations between surface discharge of polymer insulator and UV detecting image.