Title |
Calculations on the Reduction Rate of Ground Level Magnetic Fields due to Varying Configurations of Overhead Transmission Line |
Authors |
민석원(Min, Suk-Won) ; 김응식(Kim, Eung-Sik) ; 박준형(Park, Jun-Hyeong) |
Keywords |
Magnetic Field Reduction ; Overhead Transmission Line ; In-span Compaction |
Abstract |
There are concerns on possible health effects from exposure to electromagnetic fields. One reflection of this concerns is the considerable controversy, delay, and cost increases involved in the construction of power lines and facilities. To cope with such challenges, in this paper we investigated magnetic fields reduction techniques such as general compaction, in' span compaction, cruciform, vertical, 3 way splits phase, and 4way splits phase. As results, we found general compaction and 4 way splits phase could reduce magnetic fields up to 90%, while cruciform, vertical, and 3 way splits phase gave lower reduction rates of 30% because these configurations were similar to a current type of low reactance arrangement. We also knew 1 spacer in span compaction was appropriate in Korea in view of effectiveness and economy. |