Title |
A Study on the Development of Corrosion Detecting System for 22.9 kV Distribution Power Line Insulation Cable |
Authors |
김용준(Kim, Yong-Jun) ; 오용철(Oh, Yong-Cheul) ; 이건영(Yi, Keon-Young) |
DOI |
https://doi.org/10.5370/KIEE.2011.60.7.1410 |
Keywords |
Eddy current sensor ; Eddy current test ; Power line ; ACSR-OC ; NDT |
Abstract |
A corrosion detecting system for 22.9 kV distribution power line insulation cable, which can travel autonomously along the live line, is proposed. Eddy current test method is employed to detect the corrosion, and the system developed here is capable of detecting internal corrosion of a ACSR-OC. Somewhat details of the electrical and mechanical mechanism of the system and traveling algorithm are introduced. Experimental results applied to the sample cables having artificial corrosion and the operating distribution lines are provided. From the result, we confirmed that the system is useful for detecting internal corrosion of a ACSR, and is expected to be a new non-destructive testing equipment in the area of diagnosis for the distribution power line. |