Title |
Calculation Method of Modification Factors for Fault Location Algorithm Using Boosting Current of Operating Electric Train in AT Feeding System |
Authors |
김철환(Kim, Cheol-Hwan) ; 김성렬(Kim, Sung-Ryul) ; 권성일(Kwon, Sung-Il) ; 조규정(Cho, Gyu-Jung) ; 김철환(Kim, Chul-Hwan) ; 송인근(Song, In-Keun) |
DOI |
https://doi.org/10.5370/KIEE.2016.65.3.504 |
Keywords |
AT Feeding system ; Fault locator ; Field test ; Modification factors |
Abstract |
In general, a fault locator is installed in Sub-Station of AT(Auto-transformer) feeding system to estimate the fault location and to protect the Korean AT feeding system. Since the line impedance characteristic is different to normal 3-phase transmission line, we need particular modification factors, which can be calculated using fault location recording data, to estimate the accurate fault location. Up to recently, forcible ground test has been used to calculate the modification factors of the fault locator. However, large amount of current is occurred when the forcible ground test is performed, and this current affects to adjacent equipments. Therefore, we proposed a novel calculation method of modification factors, arbitrary trip test, using boosting current of the operating electric train. Through several field test, we confirmed that modification factors for fault locator can be easily calculated by using proposed method. Moreover, we verified the accuracy and stability of the proposed calculation method. |