• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title The Characteristics of the Over-current of Shielded Cable and the Fusing Current of Carbon Fiber
Authors 김영석(Kim, Young-Seok) ; 김택희(Kim, Taek-Hee) ; 김종민(Kim, Chong-Min) ; 송길목(Shong, Kil-Mok)
DOI https://doi.org/10.5370/KIEE.2016.65.10.1761
Page pp.1761-1766
ISSN 1975-8359
Keywords Carbon fiber ; Metal-coated carbon fiber ; Fusing current ; Shielding cable
Abstract In this paper, we investigated the fusing current of carbon fiber and thermal properties of carbon fiber and metal shielded cable due to over-current. The fusing current value for the metal-coated carbon fiber was 5.3A in 3K, 7.4K and 13.05A in 12K. And if it exceeds 50% of the fusing current was broken with a rapid voltage rise. In the case of carbon fiber shielded cable, the temperature of the PVC sheath increased somewhat in the allowable current range. However, the temperature of PVC sheath rapidly increased to 128.1°C in the 2 time allowable current range. This value is 10°C higher than the temperature of PVC sheath on the metal screen cable, because the resistance of the carbon fiber is high and heat transfer rate is slow.