Title |
Fault Diagnosis Device for Fire Prevention of the Resistance Heating Type three-Phase Electric Heater |
Authors |
이문형(Lee, Mun-Hyung) ; 김찬오(Kim, Chan-O) |
DOI |
https://doi.org/10.5370/KIEE.2017.66.11.1669 |
Keywords |
Electric heater ; Electric fire |
Abstract |
In this study, We have discussed the development of a diagnostic device to detect and prevent electrical fire due to the arc caused by contact failure and partial disconnection at the connection part of the three-phase electric heater wiring used in the industrial field. The arc caused by contact failure and partial disconnection at the connection part of the electric heater shows a change in the current effective value. Therefore, it is possible to determine whether there exists a defect by analyzing the current unbalance factor and the number of current fluctuations with the diagnostic apparatus. The three-phase unbalanced heater is considered to be capable of determining defects through periodic measurement and trend analysis of the current unbalance factor. It is also expected that this device can be used not only for electric heaters but also for detection of defects in wiring and connections of electrical equipment having a characteristic of constant load current. |