Title Fault Location Estimation Technique for AC Railway Power Supply System Considering of the Other Line’s AT Boosting Current Characteristics
Authors 정호성(Hosung Jung) ; 김주욱(Joo-Uk Kim) ; 김형철(Hyungchul Kim) ; 민명환(Myung-Hwan Min) ; 안태풍(Tae-Pung An)
DOI https://doi.org/10.5370/KIEE.2019.68.11.1482
Page pp.1482-1488
ISSN 1975-8359
Keywords AC railway power supply system; AT boosting current; Fault location estimation; Other line’s boosting current characteristics
Abstract This paper presents an improved fault location estimation algorithm to reduce the fault location estimation error ratio in AT boosting current ratio technique. The domestic AC traction system uses the AT feeding system as a standard, and most of the lines are composed of double tracks(up and down lines). It was confirmed that the fault location estimation error is increased due to the change of the AT boosting current of the faulted line due to the other line’s AT boosting current characteristics. Therefore, in this paper, an improved fault location estimation algorithm is proposed by using all AT boosting currents considering of the other line’s boosting current characteristics. In order to evaluate the proposed algorithm performance, the AC railway power supply system is modeled and various fault simulations were performed using the power analysis program. As a result, when comparing the error of the existing technique and the improved technique, the improved algorithm shows an average error of 0.16%, and even the maximum error is 0.88%, which is satisfied within 2% of the domestic standard.