A Study on the VLF-TD Test for Medium Voltage Cable Connected on the Motor |
Authors |
김태훈(Tae-Hoon Kim) ; 박진엽(Jin-Yeub Park) ; 차지현(Ji-Hyun Cha) ; 강민구(Min-Goo Kang) |
DOI |
https://doi.org/10.5370/KIEE.2020.69.8.1263 |
Keywords |
VLF-TD; MV Cable; Insulation |
Abstract |
The VLF-TD test, used as an insulation diagnostic method for high voltage cables, had to be performed with the load disconnected. If the cable is connected to the Motor during the VLF TD test, the leakage current of the cable and the leakage current of the load are measured together, so that it is difficult to accurately determine the state of the cable. In this paper, we conducted a VLF-TD test with the cable connected in the load and studied the method of calculating the VLF-TD test result of the cable using an equivalent circuit. |