• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title The Effect of Mechanical Wear on the Contact applied to 170kV Gas Insulated Switchgear(GIS)
Authors 한기선(Ki-Sun Han) ; 이종건(Jong-Geon Lee) ; 주형준(Hyung-Jun Ju) ; 강지원(Ji-Won Kang)
DOI https://doi.org/10.5370/KIEE.2020.69.11.1668
Page pp.1668-1674
ISSN 1975-8359
Keywords Accelerated test; Contact; Gas Insulated Switchgear(GIS); Mechanical wear; No-Load Contact Operation
Abstract This paper deals with the effect of mechanical wear on the contact of circuit breaker applied to the 170kV Gas Insulated Switchgear (GIS). The arc occurrence was ignored to verify the pure effect of mechanical wear on the contact of circuit breaker. Since only the effect of the mechanical wear was considered, the experiment was carried out under no-load state. The accelerated test method was adopted and the specimens were operated until the lifetime same as actual 170kV GIS contact. The specimens were tripped and closed up to 20,000 times and the its electrical resistances and weights were measured at regular intervals. Based on the test results, the correlation between mechanical wear of contact and trip/close coil current was analyzed. The analysis result showed that, even the slight mechanical wear of contact can cause delays in the trop/close operation of the GIS.