Title |
Proposal and Analysis of a DC Superconducting Fault Current Limiting Circuit Breaker with Adjustable CLR |
Authors |
박찬묵(Chan-Muk Park) ; 김수현(Su-Hyeon Kim) ; 임성훈(Sung-Hun Lim) |
DOI |
https://doi.org/10.5370/KIEE.2024.73.11.1924 |
Keywords |
DC superconducting current limiting (SCL) circuit breaker (CB); adjustable current limiting reactor (CLR); superconducting (SC) elements; DC fault current limiting and interrupting operation |
Abstract |
This paper suggests DC superconducting current limiting (SCL) circuit breaker (CB) that consists of two mechanical switchs (SWs), adjustable current limiting reactor (CLR) and two superconducting (SC) elements. The suggested DC SCL-CB can have advantage to perform DC fault current limiting and interrupting operation and two SWs’ sequential opening operation comprising DC SCL-CB by control circuit can protect two SC elements from DC fault current as well. Through DC short-circuit tests, SW1 was confirmed to alleviates the power burden on SC1 element and lower turn ratio of adjustable CLR was analyzed to be contributed to fast interrupting operation of SW2 by quench of SC2 element. |