구희석
(Hui-Seok Gu)
1iD
박상용
(Sang-Yong Park)
2iD
최혜원
(Hye-Won Choi)
3iD
최효상
(Hyo-Sang Choi)
†iD
-
(Energy Innovation Industry R&D Dept. at Green Energy Institute.)
-
(Dept. of Electrical Engineering, Chosun University, Korea.)
-
(Wind·Ocean Power R&D Dept. at Green Energy Institute.)
Copyright © The Korean Institute of Electrical Engineers(KIEE)
Key words
Superconducting fault current limiter, Winding type, Magnetic field, Magnetic flux density, Superconducting wire
1. Introduction
With the recent increase in electric power demand, studies on renewable energy sources
and connection to direct current (DC) systems that utilize distributed power sources
have been actively conducted worldwide (1-3). DC systems have smaller losses than alternating current (AC) systems in terms of
long-distance power transmission. Therefore, DC can compensate for insufficient power
supply through connection to the Northeast Asian Super Grid high-voltage direct current
(HVDC) because it is favorable for long-distance power transmission (4-5). For DC, however, the circuit breakers that block the fault current in the event
of a fault are insufficient. In DC systems, it is difficult to block the fault current
because there is no natural zero point, unlike in AC systems. In addition, DC generates
high arcs in the blocking process, thereby causing secondary damage by fire and explosion
(6). Therefore, for blocking systems to be used in HVDC systems, research must be conducted
on arc extinction and safety in the blocking process, as well as on highly reliable
blocking systems. As such, in this study, a superconducting DC blocking technology
was proposed by combining the existing fault current limiting technology that uses
superconductors with a DC circuit breaker. The use of superconductors can ensure reliability
because the fault current is limited in a stable manner and the blocking operation
is completed within a few milliseconds by the DC circuit breaker (7-8). The optimal winding type of the superconducting wire, which limits current, was
derived in this study. For superconductors that limit the fault current, the current
limitation is delayed as the inductance increases. Therefore, the blocking performances
was compared and analyzed through the current limiting rate, quenching time of the
superconductor, and the operation completion time of the DC circuit breaker.
2. Characteristics of each winding type
2.1 Theory
In terms of energy, the unit of work can be expressed in units such as calorific value.
This can be confirmed by 식(1) and 식(2). The amount of work is determined by the relationship between the strength of the
magnetic field and the magnetic flux density. Therefore, the amount of heat generated
is proportional to the intensity and magnetic flux density of the magnetic field generated
in the coil. In the case of superconductors, the closer the magnetic field strength
is, the closer the critical field is. At this time, the impedance is generated as
the superconductor transitions to the phase conduction state with the quench phenomenon.
Depending on the winding types, the generation of magnetic field and the increase
of magnetic flux density of the superconductor can induce fast quench characteristics.
Therefore, in this paper, spiral and helical types, which are general winding methods,
were designed using Maxwell program. The difference between the lengths of the superconductor
and the magnetic field is generated by two winding types. As the quench speed of the
superconductor is shortened, it is possible to secure the fast breaking characteristic
of the DC circuit breaker that constrains and blocks the fault current.
$W_{s}$: magnetic energy of superconducting coil,
$H$ : magnetic field strength of superconducting coil,
$B$ : magnetic flux density of superconducting coil,
$Q_{s}$: calorific value,
$V_{s}$: voltage flowing in the superconducting coil,
$I_{s}$: current flowing in the superconducting coil
표 1. 각 선재 유형에 대한 설계 파라미터
Table 1. Design parameters for each wire type
Type
|
Spiral
|
Helical
|
Number of turns [turn]
|
4
|
5
|
Length [mm]
|
3
|
4
|
Height [mm]
|
-
|
100
|
Innermost diameter [mm]
|
200
|
-
|
Outermost diameter [mm]
|
250
|
Pitch [mm]
|
8
|
Thickness [mm]
|
1
|
Width [mm]
|
10
|
Inductance [mH]
|
Calculated value
|
0.07
|
Measured value
|
0.07
|
2.2 Modeling and magnetic field distribution using the Maxwell program
표 1 shows the coil design of the superconducting current-limiting part. 그림 1(a) and (b) show the results of the analysis of each wire type’s magnetic field characteristics
using Maxwell simulation. In Maxwell simulation, the magnetic flux density can be
expressed as shown in 식 (3). The simulation analysis results showed that the magnetic flux density of the spiral
wire type was 0.850 T, and its magnetic field intensity was 67.680$\times 10^{4}$
A/m. For the helical wire type, on the other hand, the magnetic flux density was 0.813
T, and the magnetic field intensity was 64.769$\times 10^{4}$ A/m. The spiral wire
type had an approximately 0.037 T higher magnetic flux density and a 2.911$\times
10^{4}$ A/m higher magnetic field intensity. As mentioned earlier, increases in the
magnetic flux density and magnetic field intensity can increase the blocking speed
of the DC circuit breaker as they increase the calorific value generated during the
quench of the superconductor. Finally, the inductance of the spiral wire type can
be calculated using 식(4) and 식(5) while that of the helical type can be calculated using 식 (6) (9-10).
그림. 1. 보빈에 감긴 각 선재 종류 및 HTS 자기장 특성
Fig. 1. The characteristics of the magnetic field of each wire type and HTS wound
on bobbin
$D_{i.n}$: Innermost diameter of the spiral coil,
W : Width of the superconductor,
S : Pitch of the superconducting wire,
N : Number of turns of the superconducting wire,
H : Height of the helical coil
2.3 Circuit design and parameters using PSCAD/ EMTDC
그림 2 shows the circuit diagram, which includes the superconducting current-limiting part
that limits the fault current, and the mechanical DC circuit breaker that blocks the
fault current, using PSCAD/EMTDC. The superconductor for limiting the fault current
was designed using 식 (7) (11). In addition, an applied voltage of 100 kV and a steady-state current of 400 A were
selected for the simulation, and the maximum fault current was set to 70 kA. As for
the superconductor, (maximum impedance) was set to 5 Ω, and (quench time constant
of the superconductor) was set to less than 2 ms. The L and C for generating resonance
were 0.01 mH and 100 uF, respectively. Finally, the surge arrest (SA) for absorbing
the residual current after blocking the fault current was set to 80 kV. Simulation
analysis was conducted by selecting the same inductance of 0.007 mH for the two wire
types.
그림. 2. PSCAD/EMTDC를 활용한 회로도 설계
Fig. 2. Design of the circuit diagram using PSCAD/EMTDC
$R_{m}$: superconductor maximum shunt resistance,
$t_{SC}$: superconductor time constant
2.4 PSCAD/EMTDC simulation results
그림 3 shows the experimental results of each wire type that used the same inductance. The
spiral wire type performed blocking approximately 0.0008 ms later than the helical
wire type, but its blocking completion time of 0.133 ms was similar to that of the
helical wire type. The resonance frequencies can be expressed using 식(8) and 식(9) through the oscillation of LC (12). Therefore, the helical wire type has a lower resonance frequency than the spiral
wire type as the number of turns increases. As a result, the fault current by LC oscillation
was increased by approximately 34 kA for the spiral wire type and by 28 kA for the
helical wire type. If the length of the superconducting wire is analyzed instead of
the same inductance, the inductance of the helical wire type increases. This further
delays the blocking of the fault current.
그림. 3. PSCAD/EMTDC를 이용한 각 선재 유형에 따른 차단 특성
Fig. 3. The characteristics of the blocking for the each wire using PSCAD/EMTDC
3. DC blocking experiments for each wire type in the current-limiting part
3.1 Experimental conditions
Experiments for each wire type were carried out under the conditions shown in Tables
2 and 3. The configuration of the equipment for the experiment can be seen in 그림 4(a). Up to 80 batteries are connected in series to simulate a DC environment. In addition,
the fault situation can be simulated using the accident generating device. The superconductor
can maintain superconductivity by the cooling system, and the experiment was constructed
so that the limited current can be cut off using a circuit breaker. Also, the circuit
diagram configuration for the blocking test is shown in 그림 4(b). For the comparison of the two wire types, the applied voltage was increased from
400 to 550 V by 50 V increments. In addition, the normal load was set to 23.4 Ω, and
the fault load was set to 1 Ω..
표 2. 각 유형에 대한 DC 차단 실험 조건
Table 2. The experimental conditions of the DC blocking for each wire type
Battery [EA]
|
Voltage [V]
|
Fault current [A]
|
Normal current [A]
|
32
|
400
|
449.78
|
17.09
|
36
|
450
|
486.75
|
19.23
|
40
|
500
|
523.71
|
21.36
|
44
|
550
|
560.67
|
23.50
|
표 3. 각 선재 타입에 대한 초전도 선재의 길이
Table 3. Length of the superconducting wire for each wire type
Type
|
Spiral
|
Helical
|
HTS Length [m]
|
3
|
4
|
그림. 4. DC 차단 실험 및 회로도
Fig. 4. DC blocking experiments equipment and circuit diagram
그림. 5. 권선 종류에 따른 고장전류, 초전도체 저항, 차단 전류 특성
Fig. 5. The characteristics of the fault current, superconductor resistance and blocking
current according to winding type
3.2 Experimental results
그림 5(a) shows the current characteristics according to the voltage. As the voltage increased,
the fault current limitation rates of the spiral wire type were found to be 9.39,
8.62, 8.52 and 11.63%. For the helical wire type, the fault current limitation rates
were found to be 5.69, 5.24, 6.01 and 7.62%. 그림 5(b) shows the impedance characteristics according to the voltage. As the voltage increased,
the impedance of the spiral wire type increased by 0.028, 0.045, 0.073 and 0.096 Ω.
The impedance of the helical type, on the other hand, increased by 0.022, 0.028, 0.045,
and 0.065 Ω. Based on the results shown in 그림 5(a) and (b), it was found that the fault current limitation ra tes of the spiral wire type were
3.70, 3.38, 2.51 and 4.01% higher than those of the helical wire type as the impedance
of the spiral wire type was 0.006-0.031 Ω higher. Finally, the blocking time according
to the voltage was analyzed using the power applied to the circuit breaker in 그림 5(c). The breaker opening times due to the introduction of the fault current were found
to be 11.01, 10.11, 9.66 and 9.15 ms for the spiral wire type, and 11.13, 10.30, 9.81
and 9.24 ms for the helical wire type. The breaker opening time of the spiral wire
type was approximately 0.09-0.19 ms faster than that of the helical wire type. Moreover,
the breaker operation completion times were found to be 12.87, 12.01, 11.56 and 11.45
ms for the spiral wire type, and 12.95, 12.26 and 11.67 ms for the helical wire type.
The spiral wire type exhibited approximately 0.06-0.25 ms faster blocking speed. 표 4 shows the experimental results of the spiral wire type, and 표 5 shows those of the helical wire type.
5. Conclusion
In this study, the characteristics of the current-limiting part for each wire type
were analyzed to select the optimal structure of the superconducting DC circuit breaker
for current limiting. First, the simulation results for each wire type were analyzed,
and it was found that the application of the spiral wire type could improve the blocking
speed by increasing the quench speed of the superconductor. Next, experiments were
carried out using a small-scale experimental setup, and it was found that the spiral
wire type exhibited up to 4.01 % higher fault current limitation rates. The spiral
wire type also exhibited up to 0.19 ms faster breaker opening time and up to 0.25
ms faster breaker operation completion time. As superconductors are expensive, it
is important to derive their maximum effect with the minimum quantity. Based on the
simulation and experimental results in this study, it is expected that the application
of the spiral wire type to the current-limiting part will improve the fault current
limiting effect and increase the blocking speed of the circuit breaker.
References
L. Chengyu, Z. Chengyong, X. Jianzhong, J. Yuke, Z. Fan, 2017, A Pole-to-Pole Short
Circuit Fault Current Calculation Method for DC Grids, IEEE Trasn., Vol. 32, No. 6,
pp. 4943-4953
Y. Wei, P. Rui, E. Joao, R. Francisco, Y. Li, Y. Chi, X. Tang, 2019, Analysis and
Inspiration of the National Load all Powered by Renewable Energy in Portugal, IEEE
Innovation Smart Grid. Technol(Asia)
F. Z. Kadda, S. Zouggar, M. E. Hafyani, 2014, Contribution to the optimization of
the electrical energy production from a Hybrid Renewable Energy system, 5th International
Renewable Energy Congress(IREC)
X. Jianzhong, Z. Sicheng, L. Chengyu, 2018, The Enhanced DC Fault Current Calculation
Method of MMC-HVDC Grid With FCLs, IEEE Journal of Emerging and Selected Topics in
Power Electronics, Vol. 7, No. 3, pp. 1758-1767
A. Kalair, N. Abas, 2016, Comparative study of HVAC and HVDC transmission systems,
Renewable and Sustainable Energy Reviews, Vol. 59, No. , pp. 1653-1675
W. R. Leon Garcia, A. Bertinato, P. Tixador, B. Raison, 2016, Full-selective protection
strategy for MTDC grids based on R-type superconducting FCLs and mechanical DC circuit
breakers, 5th IET International Conference on Renewable Power Generation(RPG)
H. W. Choi, H. S. Choi, I. S. Jeong, 2017, Characteristics Analysis of Superconductivity
DC Interrupting System in the Grid-Connected PV System with EMTDC/ PSCAD, 16th International
Superconductive Electronics Conference(ISEC)
H. S. Gu, S. Y. Park, 2019, Failure Characteristics Analysis of DC Circuit Breaker
According to Type of Current Limiting Unit Using Superconductor, Korean Institue.
Electrical Engineer, Vol. 68, No. 12
S. S. Mohan, M. M. Hershenson, S. P. Boyd, 1999, Simple accurate expressions for planar
spiral inductances, IEEE Journal of Solid-State Circuits, Vol. 34, No. 10, pp. 1419-1424
J. W. Kim, H. H. Ji, Y. G. Choi, Y. H. Yun, K. H. Kim, 2010, Study on Arrangement
of Self-Resonant Coils in Wireless Power Transfer System Based on Magnetic Resonance,
The Journal of Korean Institute of Electromagnetic Engineering and Science, Vol. 21,
No. 6, pp. 564-572
H. Y. Choi, I. S. Jeong, S. Y. Park, 2018, Characteristics of Superconducting Coil-Type
DC Fault Current Limiter to Increase Stability in the Grid Connection PV Generation
System, IEEE Transactions on Applied Superconductivity, Vol. 28, No. 3, pp. 5600904
I. S. Jeong, H. Y. Choi, 2018, Analysis of S-Parameter Using Different Materials for
the WPT Resonance Coil, IEEE Transactions on Applied Superconductivity, Vol. 28, No.
3, pp. 0500405
저자소개
Graduated from the Department of Mechatronics Engineering, Chosun University in 2018,
Graated from the same graduate school in 2020 (Master of Engineering).
Currently Researcher of Energy Innovation Industry R&D Dept. at Green Energy Institute.
Graduated from the Department of Electrical Engineering, Chosun University in 2016.
Graated from the same graduate school in 2018 (Master of Engineering). 2018-present:
graduate school (complete a doctorate)
Graduated from the Department of Electrical Engineering, Chosun University in 2012.
Graduated from the same graduate school in 2014 (Master of Engineering). Graduated
from the same graduate school in 2019 (Doctor of Engineering).
Currently Senior Researcher of Wind·Ocean Power R&D Dept. at Green Energy Institute.
graduated in electrical engineering from Chonbuk National University in 1989, graduated
in Electrical Engineering from Graduate School in 1994, graduated in Electrical School
in 2000, Ph.D. Professor of exchange at Tennessee University, currently a professor
of electrical engineering at Chosun University