박상용
(Sang-Yong Park*)
1iD
최효상
(Hyo-Sang Choi†)
†iD
-
(Dept. of Electrical Engineering, Chosun University, Korea.)
Copyright © The Korean Institute of Electrical Engineers(KIEE)
Key words
Superconducting element, LC divergence oscillation, DC circuit breaker, PSCAD/EMTDC
1. 서 론
In order to reduce carbon emissions worldwide, the scope of use of new and renewable
energy sources is expanded, and policies are being implemented to pursue changes in
electric models in internal combustion engines. As the number and capacity of new
and renewable energy sources are expanded, the range of DC systems is also expanding.
Recently, a project is underway to expand the multiplexed structure from LVDC to HVDC
systems. As such, the number and capacity of DC loads increase, and the appearance
of the multiplexed structure of the DC system is likely to be the current state. Therefore,
we have to prepare for the transient state of the DC grid in accordance with the multiplexed
structure of the DC grid network (2).
We are conducting a research on a DC cut-off technology based on the most representative
solar power of renewable energy for reliable system operation. The mechanical DC circuit
breaker used has a structure suitable for the low breaking capacity of the LVDC. However,
it is expected that several generation facilities of the solar power will gather and
link to form a highly reliable system. Then, a multiplexed photovoltaic grid is formed,
and when an unavoidable failure occurs for the DC system, a higher fault current is
generated than that of a single system failure. We are working on to the solar power
system to which the existing mechanical DC circuit breaker is connected. Also, we
are working on to confirm whether the DC system can be a reliable DC system even with
the change of the multiplex system by applying the LC divergence oscillation circuit
and the superconducting element (3-5). We proposed a model that combines a superconducting current limiter, a mechani-
cal DC circuit breaker, and an LC divergent vibration circuit. The superconducting
element can reduce the high initial fault current within about 2 ms through the quench.
Its material is GdBCO. Mechanical DC circuit breaker has no power loss and higher
mechanical strength than semiconductor switch. Therefore, it is a switching structure
that can strongly respond to the DC fault current. However, due to the relatively
slow the opening speed of the cut-off contact, it cannot respond directly to the rapid
growth of the DC fault current. To solve this problem, we used the superconducting
element with a mechanical DC circuit breaker. We want to analyze the characteristics
of the cut-off operation generated through the hybrid method and determine the suitability.
We analyze the operation characteristics of the mechanical DC circuit breaker used
in solar power system. Also, based on this data, we analyze the cut-off operation
characteristics of the model applying the superconducting element and the LC divergent
oscillation circuit are analyzed through PSCAD. In addition, a simulation analysis
of the breaking capacity of the model applying the superconducting element and the
LC divergent oscillation circuit will be conducted.
2. 본 론
2.1 Operating characteristics of the mechanical DC circuit breaker
An experiment was conducted on the operating characteristics of a mechanical DC circuit
breaker applied to a solar power system. The mechanical DC circuit breaker model is
BK63H DC, and it has a terminal structure of the lug type and a method of the thermal-magnetic
overcurrent trip. A rated voltage is 500 V and a rated current is 50 A. The rated
voltage and current were set and tested in the DC simulation system. We simulated
a short circuit by quickly switching between a normal line and a transient line using
the switch of the SCR semiconductor type. The normal load connected to the normal
line is about 10 Ω and the fault load connected to the transient line is about 1 Ω.
Figure 1 is a graph of the cut-off operation characteristics shown the experiment data of
a mechanical DC cut-off switch through a short-circuit fault. As the test system,
a rated voltage and current are about 500 V and 50 A was set. Figure 1-(a) is about 19.4 ms when the fault occurred. The initial fault current generated through
the experiment was generated from about 47 A to about 501.6 A for about 0.3 ms. This
is the rate of increase of the HVDC fault current and the time constant is about 0.1.
Figure 1-(b) shows the time when about 14.85 ms passes after the fault current occurs and the
opening operation of the mechanical DC circuit breaker occurs. From this point on,
an arc voltage is generated by the opening operation of the cut-off contact, and the
fault current is reduced. Figure 1-(c) is point of the cut-off operation completed about 54.16 ms. When the fault current
was completed, a transient recovery voltage occurred, which occurred from about 54.25
ms to about 639.5 V. This occurred at about 54.95 ms with a rated voltage of about
500.7 V. The total time of the shutdown was about 35.55 ms due to the single shutdown
operation of the mechanical DC circuit breaker.
그림 1 초전도 소자와 LC발산진동회로가 없는 기계식 차단기의 동작 특성 실험 그래프
Fig. 1 Graph of experimental results of mechanical DC circuit breaker without the
superconducting element and LC divergence oscillation circuit
2.2 The operating characteristics of a mechanical DC circuit breaker that combines
the LC diver- gent oscillation circuit and SPD
Figure 2 is an experimental graph in which an LC divergent oscillation circuit is applied
to the mechanical DC circuit breaker. The applied voltage and loads (normal and transient)
are the same as experimental condition of the mechanical DC circuit breaker in Figure 1. Figure 2 shows a model which is the mechanical DC circuit breaker with the LC divergent oscillation
circuit. The LC divergent oscillation circuit is composed of L and C connected in
series. L and C are set as follows to match the resonance frequency according to the
generated the fault current. L is about 15 uH and C is about 750 uF. This is the time
point of the accident in Figure 2-(a), and the fault occurred in about 799.8 ms. As for the fault current, an initial fault
current of about 541.9 A occurred in about 803.3 ms. From the time the fault occurred,
the flow of current was confirmed by the reactor of the LC divergence oscillation
circuit. The initial fault current on the LC circuit is about 67.3 A occurred. Figure 2-(b) shows the point of the time when the cut-off contact of the mechanical DC circuit
breaker is open and it is about 812.4 ms. In the LC divergent oscillation circuit,
current was generated in the form of insufficient braking. Accordingly, it affected
the fault current flowing through the mechanical DC circuit breaker and affected the
amplification of the initial fault current. Figure 2-(c) shows the point at which the fault current flowing through the mechanical DC circuit
breaker reaches zero, which is about 824.1 ms. After that, the fault current all flowed
through the LC divergent oscillation circuit, and a current of about 294.7 A was generated.
Figure 2-(d) shows the point of the time when the fault current cut-off is completed, which is
about 837.1 ms.
그림 2 초전도 소자가 없는 기계식 LC 발산진동회로가 적용된 기계식 차단기 동작 특성 실험 결과 그래프
Fig. 2 Graph of experimental results of mechanical DC circuit breaker applied LC divergence
oscillation circuit without the superconducting element
2.3 Simulation modeling of DC circuit breaker using superconducting fault current
limiter
Figure 3 is a circuit diagram of a superconducting DC breaker. We modeled the DC system with
the same experi- mental conditions as the mechanical DC circuit breaker by simulation
through the PSCAD/EMTDC program. The rated voltage and current are 500 V, 50 A. The
configuration is designed with a solar power with DC power, L is the line impedance,
and the Superconducting module is a superconducting element. We made a superconducting
fault-current-limiter using the GdBCO material. We confirmed the parameters the operating
characteristics input to the superconducting module of the simulation through the
experiments. We obtained data on the rate of change from the superconducting state
to the normal state and the data of the generated resistance through experiments.
The data of the superconducting module were formulated and applied to the PSCAD/EMTDC
program (6). Arc model is a model input by formulating arc characteristics that can be realized
in simulation. In particular, the superconducting fault current limiter model was
designed based on Equation (1) and the Arc model based on Equation (2). $R_{SC}$ is
quenching resistance of the superconductor. $R_{m}$ is the maximum quenching resistance
of the superconductor. $T_{SC}$ is the time constant for the operating characteristics
of the fault current. ${g}_{m}$ is the arc conductance. $\tau_{m}$ is the arc time
constant. $U_{}arc$ is the arc voltage. $I_{}arc$ is the arc current. $P_{o}$ is the
cooling power constant.
Mechanical switch is a mechanical DC circuit breaker, and an LC divergent oscillation
circuit in which a reactor and a capacitor are connected in series are connected in
parallel. In addition, SPD is connected in parallel to extinguish residual current.
In the simulation, we designed the SPD with a smaller blocking capacity than SA. Normal
load and fault load were configured. The simulation was compared and analyzed with
two models.
그림 3 초전도 DC 차단기의 회로 구성
Fig. 3 Configuration circuit of superconducting DC circuit breaker
2.4 Simulation results
Figure 4 is a graph of the operation characteristics of the first model, and the superconducting
element is not combined. Figure 4-(a) is about 0.1 sec at the time of the accident. The time constant of DC power was designed
to be 0.1. Fault current was generated about 500 A from the start of the accident,
and the opening operation of the mechanical DC circuit breaker was performed in Figure 4-(b), and it was about 0.1126 s. Based on the preceding experimental data, the opening
point of the mechanical DC circuit breaker was designed. After the opening operation
started, an arc voltage was generated between the cut-off contacts. This arc charac-
teristic was designed by applying Mayr's arc model. The resonance of the LC divergence
oscillation circuit occurred, affecting the flow of the fault current. The fault current
in Figure 4-(c) is about 0.1162 s when the fault current reaches the artificial zero-point. Figure 4-(d) is about 0.1175 s when cut-off is completed. Figure 5 is a graph of the operation characteristics of the second model, which is a model
combined with a superconducting element. The simulation conditions are the same as
before. Figure 5-(a) shows the time of the accident, which is about 0.1 s. This model is a model to which
a superconducting element is applied, and the quenching of the superconductor is designed
at about 0.1015 s after the fault, and the superconducting threshold resistance is
designed to be about 0.8 Ω. Due to the quenching of the superconducting element, the
fault current was limited to about 279 A. Figure 5-(b) is the point of the time that is opening operation of the mechanical DC circuit breaker
and is about 0.1126 s. Figure 5-(c) shows the point of the time when the artificial zero-point of the fault current occurred
and was about 0.1129 s. This was about 3.3 ms faster than when the superconducting
fault current limiter was not applied. Figure 5-(d) is about 0.1135 s at the time of cut-off completion. This was about 4 ms faster than
the first model.
그림 4 실험 결과를 바탕으로 설계된 시뮬레이션 모델의 동작 특성 그래프
Fig. 4 Graph of the operating characteristics of the simulation model designed based
on the experimental results
Table 1 shows the results of experiments and simulations. ① is a model composed of only mechanical
DC circuit breaker. ② is a model composed of the mechanical DC circuit breaker and
LC divergent oscillation circuit. ③ is a model composed of the mechanical DC circuit
breaker, LC divergent oscillation circuit and superconducting module. The Figure 1 is the experiment ①. The Figure 2 is the experiment ①+②. The Figure 3 is the simulation ①+②. The Figure 4 is the simulation ①+②+③. In each case model, the time when the artificial zero point
occurred and the time when the fault current was completely cut-off were summarized.
그림 5 실험 결과를 바탕으로 설계된 두 번째 시뮬레이션 모델의 동작 특성 그래프
Fig. 5 Graph of the operating characteristics of the second simulation model designed
based on the experimental results
그림 6 초전도 소자의 유무에 따른 기계식 DC 차단기의 전력 부담 비교 그래프
Fig. 6 Graph of the power burden of the mechanical DC circuit breaker Depending on
the presence or absence of a superconducting element
2.5 Power burden
Figure 6 shows the comparison data of the power burden according to the application of superconducting
elements in a graph based on the simulation data of Figure 4 and 5. Figure 6-(a) shows the point of the time when the fault occurred, and it was about 0.1 s. Figure 6-(b) is the point of the time when the circuit breaker is opened, and it is set identically
to compare the data on the power burden. Its value was about 0.1126 s. The time of
the mechanical contacts opening depended on the opening characteristic of the BK63H
DC circuit breaker. Figure 6-(c) is the point of the time when the blocking when there is a superconducting element
is completed. Its value was about 0.1135 s. The power burden at this time was about
0.068 W. Figure 6-(d) is the point of the time when blocking is completed when there is no superconducting
element, and the value is about 0.1181 s. The power burden at this time was about
0.092 W. Depending on the presence or absence of a superconducting element, the following
operating characteristics were positively generated. First, the growth rate of DC
fault current was suppressed by about 55.8 %. Second, the level of the cut-off current
from the DC circuit breaker's position was formed to be low. Third, the voltage level
of the TRV(transient recovery voltage) was formed lower by 64.6 %. Fourth, it was
confirmed that the power burden of the mechanical DC circuit breaker was reduced by
about 73.9 %.
표 1 실험과 시뮬레이션 결과표
Table 1 Results of the experiment and simulation
|
Composition
|
Artificial current zero-point [ms]
|
Cut-off operation completed [ms]
|
Experiment
|
①
|
-
|
16.1
|
①+②
|
24.3
|
37.3
|
Simulation
|
①+②
|
16.2
|
17.5
|
①+②+③
|
12.9
|
13.5
|
3. 결 론
We analyzed the operation characteristics of superconducting DC circuit breaker by
simulation. We confirmed the operation characteristics of the mechanical DC circuit
breaker and the LC divergent oscillation circuit except for the superconducting module
through experiments and the combined model of the superconducting module was confirmed
through simulation. The simulation model of the mechanical DC circuit breaker was
applied the operation characteristics of the general mechanical DC circuit breaker
which is the actual equipment of the photovoltaic power generation. In addition, we
manufactured the LC divergent oscillation circuit and applied to the mechanical DC
circuit breaker. We confirmed the operation characteristics of the mechanical DC circuit
breaker according to the presence or absence of the LC divergent oscillation circuit
through the experiment. Based on the experimental data, a simulation was constructed
and a superconducting module was applied. As a result, it was confirmed that the growth
slope of the fault current decreased according to the quenching of the super- conducting
module. In addition, the method of the zero point generation of the LC divergent oscillation
circuit helped the quenching operation of the superconducting module to minimize the
power burden of the mechanical DC circuit breaker. we were able to confirm the improvement
of the superconducting module and we intend to conduct the experiment by making a
superconducting model based on the simulation data.
Acknowledgements
This research was supported by Korea Electric Power corporation [grant number: R21XO01-32]
References
M. Rautkivi, M. Kruisdijk, 2013, Future Market Design for Reliable Electricity Systems
in Europe, present. at the POWER GEN Europe’13
F. Zheng, C. Deng, L. Chen, S. Li, Y. Liu, Y. Liao, 2015, Transient Performance Improvement
of Microgrid by a Resistive Superconducting Fault Current Limiter, IEEE Transactions
on Applied Superconductivity, Vol. 25
B. Xiang Zhiyuan, L. Yingsan Geng, S. Yanabu, 2015, DC Circuit Breaker Using HTS for
Current Limiting, IEEE transac- tions on applied superconductivity, Vol. 25, No. 2,
pp. 1-7
B. Xiang, M. Junaid, L. Gao, Z. Liu, Y. Geng, J. Wang, S. Yanabu, 2019, Effects of
short circuit currents on quench and recovery properties of YBCO Tapes for DC SFCL,
IEEE transactions on Applied Superconductivity, Vol. 29, No. 2, pp. 5600706
P. H. Schavemaker, L. V. D. Sluis, 2000, An improved Mayr-type Arc model based on
current-zero measurements, IEEE trans on power delivery, vol. 15, Vol. no. 2
S. H Hwang, 2017, A Study on Superconducting Interruption System for Reducing of Power
Burden in DC Syste, Master’s Thesis Chosun University Graduate School
저자소개
Graduated from Chosun University Graduate School in 2018 (Master of Engineering).
Cur- rently completing the PhD program at the same graduate school.
Regular member of the Korean Electrical Society Major Research Areas of Interest :
Applications of superconducting Power system, Applications of DC circuit breaker
Tel: 062-230-7054
E-mail : sangyong4400@gmail.com
Currently Professor, Department of Electrical Engineering, Chosun University, 2021
~ Vice President of the Korean Electrical Society.
Major Research Areas of Interest : Applications of superconducting Power system, Applications
of DC circuit breaker, wireless power transmission.
Tel: 062-230-7025
E-mail : hyosang@chosun.ac.kr