1. Introduction
The worldwide advancement of industrialization leads to higher energy usage, which
leads to the ongoing utilization of fossil fuels. The increased release of carbon
dioxide into the atmosphere due to burning fossil fuels has expedited the process
of global warming, giving rise to significant environmental apprehensions. There's
a possibility that electricity production from renewable sources as solar panels,
wind turbines, and biomass could replace the generation of electricity from fossil
fuels. The growing need for environmentally friendly energy is causing a rise in interest
towards distributed generation systems. These systems typically function either independently
or by connecting to the main power grid. Specifically, when it comes to distant locations,
operating independently proves to be more cost-effective compared to connecting to
the grid. Nonetheless, in real-world scenarios, the devices linked to the power source
may not be evenly distributed. Owing to being necessary component of distributed power
supply, the 3-phase converter is expected to possess the capability to handle an imbalanced
load during standalone operation and furnish a stable alternating current voltage
(1). Additionally, the different wear-out conditions in each phase of converter is another
issues. The simplest active thermal control solution is reducing the switching frequency
of converter to decrease the number of commutation, resulting in prolonging lifetime
of converter (2). However, this solution lowers the output performance of converter. Using different
output power in each phase is another straightforward implementation but it requires
specific converter topology to guarantee accurate operation (3), (4). Therefore, various 3-phase 4-wire converters are developed for per-phase control
by using different output power as well as operating in unbalanced conditions.
As for 3-phase 3-wire converter, this type of converter is usually used in feeding
balanced three-phase loads. Since lack of a path for counteracting unbalanced current,
instances of imbalanced loads will result in uneven voltages across the phases of
the load. In situations of severe imbalance, the phase voltage across a load might
approach the line voltage, posing a danger. Concurrently, the 3-phase 4-wire system
has the capacity to supply power to both well-balanced 3-phase loads and those that
are not balanced, including single-phase loads. The inclusion of a neutral wire facilitates
a path for addressing uneven current, allowing the 3-phase 4-wire converter to manage
the neutral current stemming from imbalanced loads or disruptions in the power grid.
In addition, the 3-phase 4-wire offers the capability of operating under different
output power in each phase. It is suitable for per-phase control to prolonging the
lifespan of the most wear-out leg in converter. Therefore, 3-phase 4-wire converters
offer an important advantage over 3-phase 3-wire converter.
Three primary configurations exist for enhancing the power quality of a 3-phase converter
when handling an unbalanced load. One such approach involves a 3-phase composite converter,
which integrates three individual single-phase converters. This arrangement remains
functional even if one phase encounters a malfunction (5). Despite the simplicity of its control method and the autonomy of each phase's control,
the redundant circuit design leads to augmented costs and physical size. Compared
to 3-arm configuration, the 3-phase 4-leg converter offers superior feeding of an
unbalanced 3-phase load due to an increased bridge arm. This design connects the midpoint
of the arm and the neutral point of the 3-phase load to a shared junction, allowing
dual current controllers to regulate the negative sequence current path, resulting
in a straightforward configuration (6), (7). However, control over the fourth leg cannot be independent. Contrasted with the
4-leg structure, the split dc-link capacitor converter can also achieve a 3-phase
4-wire configuration, establishing a pathway for neutral current. This significantly
enhances the converter's capacity to accommodate unbalanced loads, and the neutral
point is clamped at half of the bus voltage through two split dc-link capacitors (8). In instances where the neutral point voltage remains stable, the split dc-link capacitor
3-phase converter can be considered as three separate single- phase half-bridge converters.
Consequently, independent control of the three phases becomes possible, effectively
mitigating the issue of output voltage asymmetry caused by unbalanced loads. However,
the split dc-link capacitor 3-phase converter faces challenges tied to the division
of capacitor voltage. This problem emerges due to the inflow of neutral current into
the capacitor or disparities between the two capacitors, which restricts its range
of applications. Consequently, a higher capacitance becomes necessary as the degree
of load imbalance increases.
In this paper, the comparison of these 3-phase 4-wire converter topologies, including
2-level 4-leg and 3-level 4-wire converters, based on output performance will be discussed
in this paper. Various types of switching devices, including both IGBT and MOSFET,
are used in these converter topologies to evaluate the output performance.
2. 2-level 3-phase 3-wire converter
The topology of the classical 2-level 3-phase 3-wire is depicted in Fig 1(a). Within this setup, there exists a dc-source coupled with a 2-level 3-phase converter,
which is linked to the load via a $LC$ filter. The 2-level 3-phase converter is comprised
of six power semiconductor switches. By proper controlling switching patterns of these
devices, the converter can generate ac waveforms of varying frequency and magnitude
output currents.
Fig 1(b) illustrates the output current waveforms of 2-level 3-phase 3-wire converter in experiment
using carrier-based pulse-width modulation (CBPWM) method. As is evident, the resultant
currents are sinusoidal and evenly distributed.
Fig. 1. (a) Typical configuration of 2-level 3-phase 3-wire converter, (b) Experimental
waveforms of output current and a-phase modulation signal using CBPWM
As indicated earlier, the conventional 3-phase 3-wire converter does not provide a
neutral wire, which makes it cannot accommodate single-phase loads or unbalanced power/load
conditions. Additionally, different aging conditions between phase legs of 3-phase
converter is a critical issue. When a phase leg is more aging than the remaining one
due to uneven stress distribution or manufacturing process, the lifespan of entire
converter will be decreased. Prolonging the lifespan of the most aged leg until the
next maintenance by reducing the corresponding phase output power is a straightforward
active thermal control solution (3), (4). Here, the most aged leg will be operated with less output power than two remaining
legs, as shown in Fig 2, to improve its lifespan. However, the conventional 3-phase 3-wire converter will
suffer potential issues with unbalanced currents and voltages. Hence, the 3-phase
4-wire converters for active thermal control through adjusting phase output power
is crucial.
Fig. 2. Different aging conditions and active thermal control technique using different
output power in each phase
3. 3-phase 4-wire converter
The first solution is using split dc-link capacitors for 2-level 3-phase converter
to form 2-level 4-wire converter, as shown in Fig 3. It is inherent that the neutral point can be directly connected to the mid-point
of split dc-link capacitor. Although owing to the simple structure, this converter
lacks feasibility due to the substantial capacitors required for regulating neutral
wire current and attaining equal voltage distribution among split capacitors under
unbalanced conditions.
Fig. 3. 2-level 3-phase 4-wire converter
Fig 4 illustrate the configuration of 2-level 4-leg converter. This 2-level 4-leg converter
comprises four identical half-bridge converters, forming four converter legs. Phase
leg of the 2-level 4-leg converter includes two switch cells and indexed by letters
a, b, c, and f. $S_{x1}$ and $S_{x2}$ (x = a, b, c, f) denote the upper and lower
switches, respectively. The neutral point of load in the 2-level 4-leg converter is
linked to the middle point of the $4^{th}$. The ac-side terminal of each leg can be
connected to one phase of a 3-phase ac grid or passive load or active load. The operation
of switches $S_{x1}$ and $S_{x2}$ (x = a, b, c), determines the corresponding phase
output voltage. When the upper switch $S_{x1}$ turns ON, the lower switch $S_{x2}$
is turned OFF because of complementary operation, the resulted converter output voltage
$v_{xf}$ equal to the dc source voltage $V_{dc}$. On the other hand, when the upper
switch turns OFF, lower switch turns ON, leading to $v_{xf}=0$. In contrast to the
2-level 3-leg converter, the 2-level 4-leg converter offers independent control capability
and achieves a greater utilization ratio of the dc-link voltage. Nonetheless, both
the quantity of switching components and the expenses associated with the 4-leg converter
increase.
Fig. 4. 2-level 3-phase 4-leg converter
In this study, CBPWM method shown in Fig 5, developed in (9), is adopted to control the 2-level 3-phase 4-leg converter. In this context, the
reference voltages, generated by including a suitable offset voltage, are compared
to a triangular carrier. This process is identical to the symmetrically arranged 3D
space vector PWM (SVPWM). The offset voltage is calculated as follows:
where $V_{\min}=\min(v_{af},\:v_{bf},\:v_{cf})$ and $V_{\max}=\max(v_{af},\:v_{bf},\:v_{cf})$.
$v_{af},\:v_{bf},\:v_{cf}$ are the reference voltages.
Fig. 5. CBPWM scheme for 2-level 3-phase 4-wire converter
The 3-level neutral-point clamped (NPC) converter is a type of multilevel converter
that presents an option for diminishing the count of series connected power switches.
As for 3-level NPC, every switching device is required to endure half of the dc-side
voltage. This characteristic leads to a decrease in the quantity of switches to be
interconnected. Furthermore, the 3-level NPC has the ability to furnish a 3-phase
ac voltage exhibiting decreased harmonic distortion in comparison to a comparable
2-level converter. Fig 6(a) depicts the configuration of a 3-level 4-wire NPC converter. The converter leg $a-$phase
is composed of four switches $S_{a1}$ to $S_{a4}$ and two additional diodes, that
is, $D_{a1}$ and $D_{a2}$. The dc-link capacitor is separated to two identical ones.
The dc-side midpoint is connected to the 3-level NPC via the clamping diode $D_{a1}$
and $D_{a2}$. Another topology of the NPC converter is the transistor-clamped converter
(TCC) or T-type converter, as shown in Fig 6(b). The TCC converter employs identical switches to those found in a conventional 2-level
converter since the half-bridge switches ($S_{x1}$ and $S_{x4}$) withstand the whole
dc-link voltage. The neutral point and each output terminal are connected by bidirectional
switches ($S_{x2}$ and $S_{x3}$). Different from the half-bridge switches the bidirectional
switches withstand only half of the dc-link voltage. In 3-level 4-wire NPC/TCC converter,
the neutral point is connected to the mid-point of split dc-link capacitor.
The operating conditions of the 3-level converter can be symbolized using switching
states. Switching state [P] signifies that the switches $S_{x1}$ and $S_{x2}$ are
at ON-state, resulting in the output pole voltage at $+V_{dc}/2$. Alternatively, switching
state [O] designates that the switch $S_{x2}$ and $S_{x3}$ are turned ON, resulting
in zero output pole voltage. The state where the switch $S_{x3}$ and $S_{x4}$ are
ON, yielding an output pole voltage of $-V_{dc}/2$ is denoted by [N]. The operating
status of the switches in the NPC converter and TCC converter are similar. In 3-level
converters, the dc-link capacitor voltage balancing is crucial requirement for accurate
operation. There are several PWM methods to control the 3-level 3-phase 4-wire converter,
such as 3D SVPWM (10), CBPWM with neutral-point (NP) balancing (11), direct PWM (12), and so on.
Fig. 6. (a) 3-level 4-wire NPC converter, (b) 3-level 4-wire TCC converter
In CBPWM with NP balancing (11), the neutral point current $i_{NP}$, which flows from the mid-point of dc-link capacitor
voltage to the converter, is adjusted. The NP voltage control is depicted in Fig 7. The sign of $\Delta v_{np}$ and output current are identified by two hysteresis
loops. If $\Delta v_{np}$ is small enough, resulting in the sign of $\Delta v_{np}$
is 0, $m=m_{\max}$. The converter operates with unipolar modulation. As an illustration,
in situations where the value of $\Delta v_{np}$ is extremely low, the balance of
dc-link capacitor voltages is already satisfactory. Consequently, there is no necessity
to modify the neutral point voltage, and the converter should naturally function with
unipolar modulation. Likewise, when the output current is minimal (approaching zero),
the supplementary switching associated with NP equilibrium will exert an inconsequential
or negligible influence on the NP voltage. Thus, it becomes more energy-efficient
for the converter to operate with unipolar modulation, resulting in reduced switching
losses. If $v_{C1}>v_{C2}$ means sign of $\Delta v_{np}$ is 1, and $i_{x}>0(x=a,\:b,\:c)$,
the requirement for $i_{NP}$ to be minimized is met, then $m=0$, resulting in bipolar
modulation. Generally, when $\Delta v_{np}$ and $i_{x}$ have the same sign, $m=0$
to minimize $i_{NP}$. On the other hand, when $\Delta v_{vp}$ and $i_{x}$ have the
opposite sign, $m=m_{\max}$ to maximize $i_{NP}$. The width of the hysteresis band
is established at 5%. A broader hysteresis band signifies a higher tolerance for pronounced
voltage imbalances, while a narrower hysteresis band necessitates more frequent switching,
leading to elevated losses.
Fig. 7. NP voltage control diagram
The direct PWM approach in (12) involves a straightforward PWM strategy aimed at reconstructing the switching sequence
to balance the NP voltage. Here, the duration of switching state [O] is divided into
states [P] and [N]. A balancing factor $B_{x}$ is defined to analyze the $\Delta v_{np}$
as follows:
Following the sign of $B_{x}$, the selection of states [P] or [N] will affect the
NP voltage. Fig 8 illustrates the generating new switching sequence process in $a$-phase to interpret
the direct PWM method. When the phase voltage of $a$-phase $v_{af}>0$, the original
switching sequence consists of only [O] and [P] states. To achieve balance NP voltage,
state [N] is added to generate new switching sequence. The new switching sequence
includes both three states. The same procedure is applied when $v_{af}<0$, the new
switching sequence is depicted in Fig 8.
Fig. 8. Generating new switching sequence for NP voltage balancing
4. Verification results
The waveform of 2-level 4-leg converter and 3-level 4-wire NPC/TCC converter are investigated
and verified through PSIM simulation results. The parameter of 2-level 4-leg and 3-level
4-wire converters are listed in Table 1.
Table 1. Parameters of the 2-level 4-leg and 3-level 4-wire converters
|
2-level 4-leg converter
|
3-level 4-wire converter
|
dc-link voltage
|
800V
|
800V
|
dc-link capacitance
|
1400μF
|
2800μF
|
Filter inductance
|
3.5mH
|
3.5mH
|
Filter capacitance
|
4.7μF
|
4.7μF
|
Load resistance
|
15Ω
|
15Ω
|
Output power
|
10kW
|
10kW
|
Output voltage
|
220V
|
220V
|
Fundamental frequency
|
50Hz
|
50Hz
|
Switching frequency
|
15kHz
|
7.5kHz
|
Fig 9 depicts the simulation waveform of 2-level 4-leg converter, 3-level 4-wire NPC and
TCC converters under symmetrical operation ($P_{a}$ = $P_{b}$ = $P_{c}$ = 3.3kW).
The resulted output currents obtained from three converters are sinusoidal and balanced.
The output current of 2-level 4-leg converter has higher average THD than 3-level
4-wire NPC/TCC converters. The line-to-line voltage before filter of 2-level 4-leg
converter correctly includes properly three voltage levels, while the 3-level 4-wire
NPC/TCC converter includes five levels in line-to-line voltage. Regarding the common-mode
voltage (CMV), the CMV of 2-level 4-leg converter ranges from 0 to $V_{dc}$, whereas
the common-mode voltage of 3-level 4-wire NPC/TCC converter ranges from $V_{dc}/3$
to $5V_{dc}/6$. The leakage current in 2-level 4-leg converter is significantly high
at RMS value of 3.57A. On the other hand, the corresponding leakage current of 3-level
4-wire NPC/TCC converter is negligible with RMS value at about only 3.3mA due to the
link between the neutral load and mid-point of dc-link capacitors. Due to the NP voltage
balancing strategy, the capacitor voltages in 3-level 4-wire NPC/TCC converter are
balanced with small ripple.
Fig. 9. simulation waveform of (a) 2-level 4-leg converter, (b) 3-level 4-wire NPC
converter, (c) 3-level 4-wire TCC converter in balanced operation
In Fig 10, the waveform of three converters under asymmetrical operation with different output
power in each phase ($P_{a}$ = 1kW, $P_{b}$ = 4kW, $P_{c}$ = 5kW) are presented.
Here, the magnitude of output currents changes correspondingly to the output power.
Meanwhile, the phase and line-to-line voltages are balanced. In 2-level 4-leg converter,
thanks to the $4^{th}$ leg, the phase and line-to-line voltages are kept balanced
with increased THD. As can be seen in 2-level 4-leg converter, the neutral current
increases and has sinusoidal form due to the unbalanced output currents. Regarding
the CMV and leakage current, they are similar to symmetrical operation. As for 3-level
4-wire NPC/TCC converter, the output current’s magnitude changes properly following
the output power. Meanwhile, the phase voltage and line-to-line voltage are kept balanced
with increased THD value thanks to the neutral connection. The capacitor voltages
are maintained in a balanced state around the standard value, with increased peak-to-peak
value compared to symmetrical operation. In terms of CMV, the peak value of CMV in
3-level 4-wire NPC/TCC converter increases, but the RMS value of leakage current is
the same to that of symmetrical operation. It can conclude that the 2-level 4-leg
converter and 3-level 4-wire NPC/TCC converter operate correctly under asymmetrical
operation without degradation in output performance.
Fig. 10. Simulation waveform of (a) 2-level 4-leg converter, (b) 3-level 4-wire NPC
converter, (c) 3-level 4-wire TCC converter in unbalanced operation
5. Performance evaluation
The output performance comparison between 2-level 4-leg converter and 3-level 4-wire
NPC/TCC converter are presented in Fig 11. In Fig 11(a), the output current average THD value comparison under the change of output power
is depicted. It can be seen that the 3-level 4-wire NPC/TCC converter has lower THD
value than that of 2-level 4-leg converter by approximately 30%. As for leakage current
comparison in Fig 11(b), the leakage current RMS value of 2-level 4-leg converter does not change under the
variation of output power. Meanwhile, the leakage current of 3-level 4-wire NPC/TCC
converter increases following the rise of output power, but it is negligible due to
the neutral connection.
Fig. 11. Performance comparison between 2-level 4-leg converter, 3-level 4-wire NPC
converter, and 3-level 4-wire TCC converter under changes of output power in terms
of (a) Output current THD, (b) Leakage current
The performance of 2-level 4-leg converter and 3-level 4-wire NPC and TCC converters
using different switching devices as IGBT and MOSFET from different manufacturers,
are investigated and evaluated. The SiC MOSFET C3M0021120K (13) with Drain-source voltage of 1200V rating and the Drain-source resistance of 21mΩ,
is used for the upper and lower switches of 2-level 4-leg converter and 3-level converter.
Because the middle switches of 3-level TCC converter and switches of 3-level NPC converter
are only blocking one half dc-link voltage, a SiC MOSFET C3M0025065K (14) with Drain-source voltage of 650V rating is used instead of 1200V rating SiC MOSFET.
Additionally, two IGBT modules FS3L25R 12W2H3_B11 (15) and FS3L40R07W2H5F_B11 (16) are used for 3-level 4-wire TCC converter and 3-level 4-wire NPC converter, respectively.
The power loss of the converter is calculated by using the Thermal module in PSIM
software with different switch types based on the device datasheets. The efficiency
is calculated by using only the output power and converter power loss. As can be seen
in Fig 12(a), when using MOSFET, the 3-level 4-wire TCC converter has the lowest power loss, while
the 2-level 4-leg converter has the highest power loss. Meanwhile, when using IGBT modules
for 3-level 4-wire NPC and TCC converters, at low output power, the power losses of
two converters are similar. At high output power, the 3-level 4-wire NPC converter
has higher power loss than 3-level 4-wire TCC converter. In Fig 12(c), the efficiency of three converters using different kinds of power switch under the
change of output power is presented. The 3-level 4-wire TCC converter using MOSFET
has the highest efficiency, while the 3-level 4-wire NPC/TCC converter using IGBT
module has the lowest efficiency.
Fig. 12. Performance comparison between 2-level 4-leg converter, 3-level 4-wire NPC
converter, and 3-level 4-wire TCC converter under changes of output power in terms
of (a) Power loss comparison when converter uses MOSFET, (b) Power loss comparison
when converter uses IGBT, (c) Efficiency comparison
6. Conclusion
In conclusion, the paper contributes to the field of power electronics by offering
a comprehensive analysis of various 3-phase 4-wire converters. As can be seen from
the performance comparison results, the 3-level 4-wire TCC converter offers the highest
efficiency when using MOSFET in power switches compared to 2-level 4-leg converter
and 3-level 4-wire NPC converter. The 3-level 4-wire NPC/TCC converter also has low
CMV and negligible leakage current composed to 2-level 4-leg converter. However, the
control of 2-level 4-leg converter is straightforward to implement in practical systems.
The comparative performance evaluation conducted in this study serves as a valuable
resource for advancing the design and implementation of efficient and reliable power
conversion systems.
Acknowledgements
이 논문은 정부(과학기술정보통신부)의 재원으로 한국연구재단 (No. 2020R1A2C1013413) 및 2021년도 정부(과학기술정보통신부)의 재원으로
한국연구재단-기후변화대응기술개발사업(2021M1A2A2060313)의 지원을 받아 수행된 연구로서, 관계부처에 감사드립니다
References
A. Lunardi, L. F. Normandia Lourenço, E. Munkhchuluun, L. Meegahapola, A. J. Sguarezi
Filho, 2022, Grid-Connected Power Converters: An Overview of Control Strategies for
Renewable Energy, Energies, Vol. 15, No. 11, pp. 4151
L. Wei, J. McGuire, R. A. Lukaszewski, 2011, Analysis of PWM Frequency Control to
Improve the Lifetime of PWM Inverter, IEEE Transactions on Industry Applications,
Vol. 47, No. 2, pp. 922-929
M.H. Nguyen, S. Kwak, 2022, Active Thermal Control Algorithm with Independent Power
Control Based on Three-phase Four-wire Converter, Trans. Korean Inst. Elect. Eng,
Vol. 71, No. 7, pp. 967-978
Y. Ko, M. Andresen, G. Buticchi, M. Liserre, 2017, Power Routing for Cascaded H-Bridge
Converters, IEEE Transactions on Power Electronics, Vol. 32, No. 12, pp. 9435-9446
B. Ren, M. Zhang, X. Zhao, X. Sun, June 2016, Research on control strategy of load
voltage unbalance problem for 3-phase combined inverter, in 2016 IEEE 11th Conference
on Industrial Electronics and Applications (ICIEA), Vol. 5, No. 7, pp. 2061-2065
M. Zhang, D. J. Atkinson, B. Ji, M. Armstrong, M. Ma, 2014, A Near-State Three-Dimensional
Space Vector Modulation for a Three-phase 4-leg Voltage Source Inverter, IEEE Transactions
on Power Electronics, Vol. 29, No. 11, pp. 5715-5726
I. Vechiu, O. Curea, H. Camblong, 03/01 2010, Transient Operation of a 4-leg Inverter
for Autonomous Applications With Unbalanced Load, Power Electronics, IEEE Transactions
on, Vol. 25, pp. 399-407
R. Zhang, D. Boroyevich, V. H. Prasad, H. C. Mao, F. C. Lee, S. Dubovsky, 27 Feb 1997,
A three-phase inverter with a neutral leg with space vector modulation, in Proceedings
of APEC 97 - Applied Power Electronics Conference, Vol. 2, pp. 857-863
K. Jang-Hwan, S. K. Sul, 2004, A carrier-based PWM method for three-phase 4-leg voltage
source converters, IEEE Transactions on Power Electronics, Vol. 19, No. 1, pp. 66-75
M. M. Prats, L. G. Franquelo, R. Portillo, J. I. Leon, E. Galvan, J. M. Carrasco,
2003, A 3-D space vector modulation generalized algorithm for multilevel converters,
IEEE Power Electronics Letters, Vol. 1, No. 4, pp. 110-114
F. Luo, K.-H. Loo, Y.-M. Lai, 2016, Simple carrier-based pulse-width modulation scheme
for three-phase four-wire neutral-point-clamped inverters with neutral-point balancing,
IET Power Electronics, Vol. 9, No. 2, pp. 365-376
F. Li, F. He, Z. Ye, T. Fernando, X. Wang, X. Zhang, 2018, A Simplified PWM Strategy
for Three-Level Converters on 3-phase Four-Wire Active Power Filter, IEEE Transactions
on Power Electronics, Vol. 33, No. 5, pp. 4396-4406
C3M0021120K Datasheetr, Cree, Inc.
C3M0025065K Datasheet, Cree, Inc.
FS3L25R12W2H3_B11 Datasheet, infineon
FS3L40R07W2H5F_B11 Datasheet, infineon
저자소개
응웬 민 호앙 (Minh Hoang Nguyen)
Minh Hoang Nguyen received the B.S. degree in electrical and electronics engineering
from Hanoi University of Science and Technology, Vietnam, in 2016.
He is currently pursuing the M.S and PhD combined degree in electrical and electronics
engineering with Chung-Ang University, Seoul, South Korea.
His research interests are control for multilevel converters.
Sang-Shin Kwak received the Ph.D. degree in electrical engineering from Texas A&M
University, College Station, TX, USA, in 2005.
From 1999 to 2000, he was a Research Engineer with LG Electronics, Changwon, South
Korea.
From 2005 to 2007, he was a Senior Engineer with Samsung SDI R&D Center, Yongin, South
Korea.
From 2007 to 2010, he was an Assistant Professor with Daegu University, Gyeongsan,
South Korea.
Since 2010, he has been with Chung- Ang University, Seoul, South Korea, where he is
currently a Professor.
His current research interests include the design, modeling, control, and analysis
of power converters for electric vehicles and renewable energy systems as well as
the prognosis and fault tolerant control of power electronics systems.